| Product Information: | DESIGN NO. DII/PH 60-03
DESIGN NO. DII/PH 60-03
PENETRATION FIRE STOPS
RATING: T & R - 1 HOUR
| 1. | FLOOR/CEILING ASSEMBLY: Any one-hour fire-rated floor-ceiling assembly rated in accordance with ASTM-E119, UL-263, NFPA-251, CAN/ULC-S101 or complying with the following: Use nominal 2 x 10 SYP wood or steel, solid or open-web joists spaced 16" oc maximum. Subfloor/underlayment (Item 1): 19/32” thick plywood with long edges T&G and 15/32” interior plywood underlayment with exterior glue subfloor perpendicular to joists with joints staggered from both adjacent subflooring and underlayment (or equivalent subfloor/underlayment) or 1” nominal wood sub and finished floor. Subfloor and underlayment fastened to joists in accordance with local building code.
NOTE: Cavity insulation is not required in this floor/ceiling assembly to achieve the 1 hour fire-resistance rating. |
| 2. | Gypsum Board Ceiling: Cover underside of joists with one layer of minimum 5/8” thick ASTM-C1396, Type X gypsum board (or equivalent). Apply gypsum board using minimum 6d, 1-7/8" long gypsum board nails spaced 6” oc maximum. Premixed joint compound applied to face layers of gypsum board in two coats to all exposed fastener heads and gypsum wallboard joints. A minimum 2" wide paper tape (or equivalent) is embedded in first layer of compound over joints in second layer of gypsum wallboard. |
| 3. | PENETRATING ITEM: Sonance 6-1/2” round metal speaker backcan assembly (Item 3) consisting of a Sonance 6-/12” round insulated metal Speaker Backcan (Part No. 91906), and a Sonance Symphony® 6-1/2” round footprint in-ceiling speaker (or equivalent speaker). Attach the Speaker Backcan to the horizontal ceiling joists at the desired location through the pre-drilled holes in the flange of the Speaker Backcan using a minimum of four (4) #8 x 1-1/4" long mechanical fasteners: one applied to each corner. Cut a hole in the gypsum board (Item 2) to match the opening in the Speaker Backcan. Apply the gypsum board (Item 2) over the Speaker Backcan so that the hole is aligned with the Speaker Backcan opening. Install the Sonance Symphony® 6-1/2” footprint in-ceiling speaker (or equivalent speaker).
NOTE: A speaker is not required in this assembly to achieve the 1-hr fire-resistance rating.
Reference the manufacturer’s installation instructions for more details about the Sonance 6-1/2” round metal speaker backcan assembly and wiring. |
DEISGN NO. DII/PH 60-04
DESIGN NO. DII/PH 60-05
DESIGN NO. DII/PH 60-06
DESIGN NO. DII/PH 60-09
DESIGN NO. DII/PV 60-01
DESIGN NO. DII/PV 60-02
DESIGN NO. DII/PV 60-07
DESIGN NO. DII/PV 60-08
| Party(s) Authorized by Manufacturer To Apply Mark: |
Sun Technique Electric Co., Ltd.
Song Mu Shon Village, Da Land Town
Dongguan City, Guangdong China |  |
|  |
 |  |  |
| Evaluated to the following: | The listed systems in this section have been evaluated to the following requirements:
ASTM-E814, Fire Tests of Through-Penetration Firestops
CAN/ULC-S115, Fire Tests of Firestop Systems
Maintenance of integrity (stay-in-place and prevent passage of flame) when subjected to the test temperatures (standard fire exposure) in:
ASTM-E119, Fire Tests of Building Construction & Materials
CAN/ULC-S101, Fire Endurance Tests of Building Construction & Materials
Test Pressure Differential - Each listing indicates a "Test Pressure Differential" which is the amount by which the pressure on the fire exposed side of the system exceeded the pressure on the unexposed side during test.
Annular Spacing - Where annular spacing is specified in these listings for through-penetration type systems it refers to the clearance between the penetration and the opening. Where a specific distance is stated and not identified as "minimum", the penetration is centered in the opening; where a distance is specified as "minimum", the maximum spacing is governed by the maximum opening size; where a range is stated, the penetration may be offset in the opening within the clearance limitations of the spacing range given.
These systems are intended for use in the types of separations for which they are qualified in the listed design. The separations themselves should be rated for the period required per ASTM-E119, CAN/ULC-S101 or equivalent.
Where only F and T ratings (ASTM-E814) are given for a system design, these correspond to FH and FTH ratings (CAN/ULC-S115) and may be read as such.
Systems are installed, unless otherwise noted, in accordance with the Manufacturer's Installation Instructions or Design Manual.
Penetrating items must be supported as required by applicable codes on both sides of the fire barrier. Listed Firestop systems that include support for the penetrating item indicate the supporting element in the listing. Such items are not evaluated for their load carrying capacity during the fire resistance test.
All listed components are identified with the WHI Certification Mark.
Manufacturers of listed components subscribe to an Intertek follow-up factory inspection and certification program. |  |
| |  |  |
| |  |  |