WALL ASSEMBLIES

JAMES HARDIE BUILDING PRODUCTS, INC. - Mission Viejo, CA USA



Show details for General InformationGeneral Information
Show details for DESIGN NO. JH/WA 60-01DESIGN NO. JH/WA 60-01
Hide details for DESIGN NO. JH/WA 60-02DESIGN NO. JH/WA 60-02
DESIGN NO. JH/WA 60-02
NON-SYMMETRICAL, NON-LOAD-BEARING WALL ASSEMBLY
1.Steel Studs: Minimum 3-5/8" depth, 25 gauge galvanized steel studs, spaced 16" oc.
2.Insulation: Stud cavities insulated with 3" thickness of 3 pcf mineral fiber batt insulation (rockwool), complying with ASTM-C665, Type I.
3.Gypsum Wallboard, Side A: 5/8" Type X gypsum wallboard installed horizontally or vertically and fastened with minimum 1" Type S drywall screws, 8" oc along floor and ceiling runners and 12" oc at intermediate studs. Joints in wallboard to be taped and filled.
4.Fibre-cement Board, Side B: 7/16" Titan® panel, Harditex® baseboard, or Hardibacker® backerboard, applied vertically with vertical edges staggered 16" and fastened with 1" long No. 8 by 0.323" HD self-drilling ribbed buglehead or equivalent furring screws, 8" oc along floor and ceiling runners and intermediate studs. Joints finished with glass fiber mesh tape and standard latex-modified thickset mortar. Titan® panel and Hardibacker® backerboard may be faced with ceramic tile.
Show details for DESIGN NO. JH/WA 60-03DESIGN NO. JH/WA 60-03
Show details for DESIGN NO. JH/WA 60-04DESIGN NO. JH/WA 60-04
Show details for DESIGN NO. JH/WA 60-05DESIGN NO. JH/WA 60-05
Hide details for DESIGN NO. JH/WA 60-06DESIGN NO. JH/WA 60-06
DESIGN NO. JH/WA 60-06
SYMMETRICAL, NON-LOAD-BEARING WALL ASSEMBLY
1.Steel Studs: Minimum 3-5/8" depth 20 gauge (0.0359") galvanized steel studs, spaced 24" oc.
2.Composite Gypsum/Fibre-cement Board: Both sides of wall are faced with one layer of 5/8" Titan®-FR panel. Boards are oriented either horizontally or vertically. Panel joints are offset by 24" from those on opposite side of wall. Panels are fastened with minimum 1" Type S drywall screws, spaced 12" oc.
Show details for DESIGN NO. JH/WA 60-07DESIGN NO. JH/WA 60-07
Show details for DESIGN NO. JH/WA 60-08DESIGN NO. JH/WA 60-08
Hide details for DESIGN NO. JH/WA 60-09DESIGN NO. JH/WA 60-09
DESIGN NO. JH/WA 60-09
NON-SYMMETRICAL LOAD-BEARING WALL ASSEMBLY; FULL DESIGN LOAD


1.Wood Studs: Nominal 2" by 4" solid sawn wood studs located 16" oc, with two top plates and a single bottom plate.
2.Insulation (Optional): Glass fiber batt insulation, conforming to CSA-A101 Glass Fiber Insulation minimum 0.6kg/m˛.
3.Gypsum Wallboard, Side A: 5/8" Type X gypsum wallboard, oriented vertically and fastened with 1-3/4" cup-head gypsum nails, spaced 7" oc at board edges and in field areas, or 1-1/2" Type S drywall screws, spaced 8" oc at board edges and in field areas of boards.
Gypsum Sheathing, Side B: 5/8" Type X gypsum sheathing fastened with 1-3/4" long roofing nails spaced 7" oc. Sheathing edge joints shall be staggered from those on opposite sides of the wall.
4.Fibre-cement Exterior Siding: 5/16" thick Hardipanel vertical siding applied as per manufacturer’s installation instructions.


Show details for DESIGN NO. JH/WA 60-10DESIGN NO. JH/WA 60-10




Show details for Evaluated to the following...Evaluated to the following...